THERMAL AND RELATIVE HUMIDITY MAPPING OF A SAMPLING ROOM
Vitalis B. Mbuya, Tenzin Tashi and H. V. Gangadharappa*
ABSTRACT
The purpose of this study was to carry out temperature and relative
humidity mapping of a sampling store room for a period of 72 h. The
study was aimed to find out if the temperature and relative humidity
distribution were uniform and maintained within the acceptance
criteria throughout the sampling room. The temperature and relative
humidity were maintained and controlled by a HVAC system. The
study was carried out using Ebro EBI 20 temperature/humidity data
loggers. A total of ten data loggers were used, which were kept at
specific locations in the room throughout the study period. Based on
the acceptance criteria of the study protocol the temperature was to be
maintained between 20°C to 25°C and the relative humidity be not
more than 65% RH. Based on the evaluation of data it was observed
the minimal temperature was 22.8°C, maximum temperature was
24.6°C, minimum relative humidity was 46.1% RH and maximum
relative humidity was 64.4% RH.
Keywords: Temperature mapping, relative humidity mapping.